D-20-9 / D-21-9 GB
WIKA Additional Instructions Pressure Transmitter with CANopen Interface D-20-9 / D-21-9 50
Example
Configure the node-is of a slave:
• Set the device to stopped mode (see 9. Network Management Objects)
• Change from operation mode to configuration mode via Switch Mode Selective
(see LSS Protocol Descriptions)
• Setting the node ID via Configure Node-ID Protocol
(see LSS Protocol Descriptions)
• Change from configuration mode to operation mode via Switch mode Global
(see LSS Protocol Descriptions)
Configure the bit timing parameters:
• Set the device to stopped mode (see 9. Network Management Objects)
• Change from operation mode to configuration mode via Switch Mode Global
(see LSS Protocol Descriptions)
• Set baud rate via Configure Bit Timing Parameters Protocol
(see LSS Protocol Descriptions)
• Activate bit timing via Activate Bit Timing Parameters Protocol
(see LSS Protocol Descriptions)
• Change from configuration mode to operation mode via Switch mode Global
(see LSS Protocol Descriptions)