Wika IPT-11 Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Urządzenia pomiarowe Wika IPT-11. WIKA IPT-11 User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - Operating Instructions

Operating InstructionsProcess pressure transmitter IPT-1* Vers. 3.0 - metalicsensor4 … 20 mADocument ID:37300

Strona 2 - Contents

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Strona 3

Fig. 2: Measures against moisture penetrationThe ventilation for the electronics housing is realised via a filterelement in the vicinity of the cable g

Strona 4 - 1 About this document

12Fig. 4: Temperature ranges1 Process temperature2 Ambient temperatureMake sure that the upper temperature limits for the environment ofelectronics ho

Strona 5 - 2 For your safety

Use the seal corresponding to the instrument:l Process fitting GD: Tesnit seal in front of the thread- or -Seal the thread with teflon, hemp or a simila

Strona 6 - 2.6 CE conformity

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Strona 7 - 3 Product description

Take note of the corresponding installation regulations for Exapplications. In particular, make sure that no potential equalisationcurrents flow over t

Strona 8 - 3.3 Operation

9 Check the hold of the wires in the terminals by lightly pu lling onthem10 Connect the screen to the internal ground terminal, connect theouter groun

Strona 9

11 24...20mADisplayFig. 7: Wiring plan, single chamber housing1 Voltage supply/Signal output5.4 Switch on phaseAfter connecting IPT-1* to power supply

Strona 10 - 4 Mounting

6 Set up with the indicating and adjustmentmodule6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay, adjustme

Strona 11 - 37300-EN-100302

Fig. 8: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea

Strona 12 - 4.3 Mounting steps

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Strona 13

6.3 Adjustment system1.1231Fig. 9: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Strona 14 - 5 Connecting to power supply

6.4 Setup procedureIPT-1* can be used for level as well as for process pressuremeasurement. Default setting is level measurement. The mode can bechang

Strona 15 - 5.2 Connection procedure

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Strona 16 - 5.3 Single chamber housing

The adjustment unit is thus switched over from bar to m.Proceed as follows to select the temperature unit:4)à Activate the selection with [OK] and sel

Strona 17 - 5.4 Switch on phase

If the adjustment ranges are exceeded, the message "Outsideparameter limits" appears. The editing procedure can be aborted with[ESC] or the

Strona 18 - 6.1 Short description

In the menu items "zero" and "span" you determine the span of thesensor, the span corresponds to the end value.Information:The ste

Strona 19

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Strona 20 - 6.3 Adjustment system

Proceed as follows:1 Edit the mbar value in the menu item "zero" with [OK].Zero000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested mbar valu

Strona 21 - 6.4 Setup procedure

If the adjustment ranges are exceeded, the message "Outsideparameter limits" appears. The editing procedure can be aborted with[ESC] or the

Strona 22

Menu section Function Reset valueSensor-TAG SensorDisplay Displayed value 1 barDisplayed value 2 %Display unit Volume/lScaling 0.00 to 100.0Decimal po

Strona 23

8.2 Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .369 Supplement9.1 Technical data . . . . . . . . . . . . . . . . . . . .

Strona 24 - 0000.0 mbar

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows may not always be available.Basic adjustment1▶Basi

Strona 25

Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1Pointerp-min.: -5.8 mbarp-max.: 167.5 mbarT-min.: -12.5 °CT-max.: +85.5 °C3.2Sensor statu

Strona 26

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Strona 27

7 Maintenance and fault rectification7.1 Maintenance, cleaningWhen the instrument is used properly, no special maintenance isrequired in normal operati

Strona 28 - Copy sensor data?

? 4 … 20 mA signal missingl Connection to voltage supply wrongà Check connection according to chapter "Connection steps"and if necessary, co

Strona 29

l If necessary, state a contaminationl Clean the instrument and pack it damage-proofl Attach the completed form and probably a safety data sheet to th

Strona 30 - 6.5 Menu schematic

8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Strona 31

9 Supplement9.1 Technical dataGeneral dataPressure type Gauge pressure or gauge pressureMeasuring principle- Measuring ranges ≤ 16 bar piezoresistive

Strona 32

Dynamic behaviour outputRun-up time approx. 10 s90 %100 %10 %ttTAttS21Fig. 10: Sudden change of the process variable. tT: dead time; tA: rise time; tS

Strona 33 - 7.2 Rectify malfunctions

Nominal range Overload capacity, max.pressureOverload capacity, min.pressure0 … 100 bar/0 … 10 MPa 200 bar/20 MPa -1 bar/-100 kPa0 … 250 bar/0 … 25 MP

Strona 34 - 7.3 Instrument repair

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Strona 35

Influence of the product or ambient temperatureThermal change zero signal and output spanApplies to the digital signal output (HART, Profibus PA, Founda

Strona 36 - 8 Dismounting

- EPDM (A+P 75.5/KW75F) -40 … +105 °C (-40 … +221 °F)- NBR (COG) -20 … +105 °C (-4 … +221 °F)Product temperature front-flush threaded fitting G1 A accor

Strona 37 - 9 Supplement

Adjustment elements 4 keysProtection rating- unassembled IP 20- mounted into the sensor without cover IP 40Materials- Housing ABS- Inspection window P

Strona 38

Electrical protective measuresProtection rating- Housing, standard IP 66/IP 6720)Overvoltage category IIIProtection class IIApprovalsDepending on the

Strona 39

9.2 DimensionsHousingM20x1,5M20x1,5/½ NPT234M20x1,5/½ NPT~ 69 mm(2 23/32")ø 77 mm(3 1/32")112 mm (4 13/32")M20x1,5/½ NPT1~ 69 mm(2 23/3

Strona 40

IPT-1* - threaded fittingSW27SW2760°23mm(29/32")G ½ A63mm(2 31/64")57mm(2 1/4")15mm(19/32")3mm(1/8")ø 3mm (1/8")ø 6mm (15

Strona 41

IPT-1* - front-flush connection, part 1SW4120,5 mm(13/16")G1B G½B65 mm(2 9/16")ø 30 mm (1 3/16")SW6022 mm(55/64")SW2720,5 mm(13/16&

Strona 42

IPT-1* - front-flush connection, part 251 mm(2 1/64")ø 84 mm (3 5/16")RT RASA ø64 mm (2 33/64")82 mm(3 15/64")3T 3R ø 65 mm (2 9/

Strona 43

WIKA Alexander Wiegand SE & Co. KGAlexander-Wiegand-Straße 3063911 Klingenberg/GermanyPhone +49 9372 132295Fax +49 9372 132706e-mail: support-tron

Strona 44 - 9.2 Dimensions

2 For your safety2.1 Authorised personnelMount and set up the pressure transmitter only if you know theapplicable national regulations and have the ap

Strona 45

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis d evice fulfills the

Strona 46

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l IPT-1* process pressure transmitterl Documentation- this operating instructio

Strona 47

l Instrument typel Article and serial number devicel Technical data: Measuring range, process pressure, processtemperature, signal output, voltage sup

Strona 48

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i

Powiązane modele: IPT-10

Komentarze do niniejszej Instrukcji

Brak uwag