Fig. 23: Measurement setup, ow measurement in liquids
1 E.g. lter
2 Blocking valves
3 DPT10
4 Precipitator
5 Drain valves
6 3-fold valve block
à Mount isolating diaphragm with capillaries on top or laterally on the
pipeline
à In vacuum applications: Mount DPT10 below the measurement
loop
à The ambient temperature should be the same for both capillaries
Fig. 24: Measurement setup, dierential pressure measurement in gases,
vapours and liquids
1 Isolating diaphragm with bolting
2 Capillaries
3 E.g. lter
4 DPT10
In gases, vapours and
liquids
26 Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA
4 Mounting
37245-EN-100120