Wika LSD-30 Instrukcja Użytkownika Strona 22

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 104
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 21
22 WIKA operating instructions level switch model LSD-30
GB
11613033.01 01/2012 GB/D/F/E
6.4 Switching functions
Hysteresis function
If the level uctuates around the set point, the hysteresis keeps
the switching status of the outputs stable. With increasing level,
the output switches when reaching the switch point (SP).
Contact normally open (HNO): active
Contact normally closed (HNC): inactive
With the level falling again, the output will not switch back before
the reset point (RP) is reached.
Contact normally open (HNO): inactive
Contact normally closed (HNC): active
Window function
The window function allows for the control of a dened range.
When the level is between window High (FH) and window Low
(FL), the output switches on.
Contact normally open (FNO): active
Contact normally closed (FNC): inactive
When the level is outside window High (FH) and window Low
(FL), the output does not switch on.
Contact normally open (FNO): inactive
Contact normally closed (FNC): active
6. Commissioning, operation
Fig.: Hysteresis function
Fig.: Window function
Przeglądanie stron 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 103 104

Komentarze do niniejszej Instrukcji

Brak uwag