11
EN
11WIKA operating instructions, models CTH63I0 and CTH65I0
14120692.01 04/2015 EN/DE
Marking Designation Meaning
ib Intrinsic safety The instrument contains an intrinsically safe
current loop. A current loop is intrinsically safe if
neither sparks nor thermal effects can cause the
ignition of a specified explosive atmosphere.
IIB Instrument group Electrical instrument group designated for
gas hazardous areas in accordance with
DIN EN 60079-0.
T4 Temperature class Maximum occurring surface temperature of
135 °C.
Gb Equipment Protection
Level (EPL)
With equipment protection level Gb, in accord-
ance with DIN EN 60079-0 (2007), a potentially
explosive atmosphere involving gases (G) may
occur occasionally. The instrument can be used in
zone 1 and zone 2.
Temperature class Maximum surface temperature
T1 450 °C
T2 300 °C
T3 200 °C
T4 135 °C
T5 100 °C
T6 85 °C
2. Safety