WIKA operating instructions dierential pressure transmitter, model DPGT4010
14093267.01 03/2014 GB/D/F/E
3. Specications
For further specications see the corresponding product label, WIKA data sheet
and the order documentation.
Designation of terminal connectors
The exact pin assignments can be found in the following drawings. In addition, the
pin assignment, output signal and the required power supply are stated on the
product label.
The following diagram shows the standard terminal assignment. For customer-
specic designs, the terminal assignment on the product label must be followed.
2-wire system
4 … 20 mA
3-wire system
0 … 20 mA, 4 … 20 mA and 0 ... 10 V
Earth, connected to
case 1)
U
B
+/I+
0 V/GND
Evaluation
(display)
1) This connection must not be used
for equipotential bonding. The
instrument must be incorporated in the
equipotential bonding via the process
connection.
Terminals 3 and 4: for internal use only
Terminals 5 and 6: reset zero point
Evaluation
(display)
Power supply
Power supply
Explanation of the terminal assignments used:
U
B
+ Positive terminal of power supply
0 V/Sig-/GND Negative terminal of power supply and output signal
Sig+ Positive terminal of output signal
I+ Output signal
Earth, connected to
case 1)
0 V/Sig-/GND
U
B
+
Sig+