WIKA operating instructions air2guide model A2G-45
13
GB
40389228.01 09/2012 GB/D/F/E/I
Inuence of the span
setting on the measured
values
Pout
10 V
Pressure
6. Commissioning, operation ... 8. Disposal
Set the span in the following sequence:
1. Carry out a zero point calibration
2. Connect the pressure connections
3. Select "Span" in the menu and then select "Adjust"
4. Using both the "up" and "down" arrow buttons, set the relevant value
for the display or the 0 … 10 V output, so that it matches the reference
pressure instrument's value
5. Conrm the setting by pressing the "OK" button
7. Maintenance and cleaning
The dierntial pressure switches are maintenance-free and oer long
service life provided they are handled and operated properly.
Clean the instruments with a moist cloth (soap water).
Repairs must only be carried out by the manufacturer or appropriately
qualied skilled personnel.