WIKA operating instructions air2guide model A2G-40
9
GB
40202771.02 07/2012 GB/D/F/E/I
6. Commissioning, operation
6. Commissioning, operation
Installation
The specications for the switching pressure refer to a vertical mounting
position. For a horizontal mounting position, the switching pressure is
changed as follows:
Case cover to the top: +15 Pa
Case cover to the botttom: -15 Pa
Electrical connection
Cable gland M16, screw terminals max. 1.5 mm²
Contact arrangement
Measuring
ranges
Contact rating Contact
material
With resistive load With inductive load
20 … 200 Pa 0.1 A / AC 250 V - Gold
30 … 300 Pa 3 A / AC 250 V 2 A / AC 250 V Silver
30 … 500 Pa 3 A / AC 250 V 2 A / AC 250 V Silver
40 … 600 Pa 3 A / AC 250 V 2 A / AC 250 V Silver
100
1,500 Pa 3 A / AC 250 V 2 A / AC 250 V Silver
500
4,500 Pa 5 A / AC 250 V 2 A / AC 250 V Silver
Contact rating
1-3 opens / 1-2 closes on reaching
the dierential pressure