Wika TR33 Instrukcja Użytkownika Strona 20

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 52
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 19
GB
14073818.01 01/2014 GB/D
20 WIKA operating instructions model TR33
Do not exceed the following values:
Version with 4 ... 20 mA output signal
Power supply and current loop circuit (connections)
Voltage U
i
DC 30 V
Current I
i
120 mA
Eective internal capacitance C
i
6.2 nF
Eective internal inductance L
i
110 µH
Sensor current loop
Power P
o
37.5 mW
Ambient temperature -40 ... +85 °C (-40 ... +185 °F)
The maximum self-heating at the sensor tip is 4 K
Version with Pt100 and Pt1000 output signal
Sensor current loop
Voltage U
i
DC 30 V
Current I
i
550 mA
Eective internal capacitance negligibly small
Eective internal inductance negligibly small
Ambient temperature -40 ... +85 °C (-40 ... +185 °F)
6.3 Behaviour of the electrical output signal
Sensor break and short-circuit
Sensor break or short-circuit are signalled after positive detection
(after approx. 1 second). If this fault condition has been caused by
a malfunction, then a relevant measurement signal must exist for
approx. 1 second in order to return to measuring mode. From the time
of the error detection up to the fault signal, the last relevant measured
value will be delivered on the current loop.
Therefore, in the event of a “true” sensor break or short-circuit, this
is also signalled permanently. In the event of a “false” sensor break
or short-circuit, the transmitter has the possibility of reverting to
measuring mode.
6. Commissioning, operation
Przeglądanie stron 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 51 52

Komentarze do niniejszej Instrukcji

Brak uwag