22 WIKA operating instructions pressure transmitter model O-10
GB
11613017.04 05/2013 GB/D/F/E
6. Commissioning, operation
6. Commissioning, operation
CAUTION!
Prior to commissioning, the pressure transmitter must be subjected to a visual inspection.
Leaking uid is indicative of damage.
Only use the pressure transmitter if it is in perfect condition with respect to safety.
CAUTION!
The model O-10 (T) pressure transmitter must not be exposed to any condensation.
6.1 Mechanical mounting
Required tool: Open-ended spanner (spanner width 24)
The sealing faces at the instrument have to be undamaged and
clean.
When screwing the instrument in, the force required to do this
must not be applied through the casing, but only through the
spanner ats provided for this purpose and using a suitable tool.
When screwing in, do not cross the threads.
For information on tapped holes and welding sockets, see
Technical information IN 00.14 at www.wika.com.
Spanner ats