WIKA operating instructions air2guide model A2G-80
9
GB
40202810.02 07/2012 GB/D/F/E/I
6. Commissioning, operation
6. Commissioning, operation
Installation
Protect air quality sensors from contamination, high temperature
changes and vibrations
Solar irradiation and air draught are to be avoided
Mount duct sensors with their air intake facing the direction of the
ow
Max. air draught 10 m/s
Electrical connections
The sensor cannot distinguish pleasant from unpleasant smells, but
in the end it is the persons living or working in the room who have to
judge whether the air quality is satisfactory or not. Moreover, dierent air
compositions are occurring in dierent rooms.
This means that the set point for the required air quality is temporarily
preset during production. Optimisation must be done when the sensor
is installed.
Individual adjustment of the output signal is made via a trim potentiom-
eter on the sensor PCB. With this, the oset of the output signal is either
raised or lowered:
1. Attach sensors, lock the cover, switch on the power supply
2. Make sure there are good air conditions close to the sensor